Description

Circuit Breaker Enclosure

 

These devices (4 poles, 3 of which are protected) use air interruption and metal-partition arc chambers for arc quenching.

When the breaker is open, a contact establishes an electrical connection between the transformer’s neutral and the system ground. When the breaker is closed, a spark gap limits the potential rise of the LV neutral relative to ground to a value above 10 kV.

The breaker is housed in a weather-resistant polyester enclosure reinforced with fiberglass.

 

Digital Trip Units

 

The Digital Trip Unit ensures protection for three transformer ratings on pole-mounted installations (50 kVA or 100 kVA for this model), whether conventional transformers (without internal protection) or new transformers with integrated protection (TPC).

A selector switch allows the user to set the appropriate transformer protection rating. The microcontroller continuously estimates the transformer’s probable temperature based on the three-phase currents and the ambient external temperature. The latter is calculated from the sensor and a mathematical model, which also takes the three phase currents into account.

If a Digital Trip Unit is integrated into an older generation pole-mounted circuit breaker, the load integrator function—if present—will be disabled.

 

 

Features

Product range
Pole-Top Circuit Breaker
Device name
D265T
Tension
440V
Power
160 KVA
Nominal stream
265 A
Nominal section
50 - 150mm²
Equipment included

Operating Rod System

Contractual guarantee
1 YEAR
Country of origin
FRANCE