Description

Rated power (kVA): 630

Rated voltages (kV/V): Dual primary 15–20 kV / 410 V (no-load secondary voltage)

High-voltage insulation level (kV): 17.5 for 15 kV – 24 for 20 kV

Tapping range (%): ±2.5%, ±5% for 20 kV; ±3.33%, ±6.67% for 15 kV

Vector group: Dyn11

Frequency (Hz): 50

Short-circuit voltage at 75°C (%): 4

Losses (W):

– No-load: 1300 W

– Load (at 75°C): 7150 W

Losses and short-circuit voltage are subject to the tolerances specified in IEC 60076.

Features

Product range
Cabin transformer
Type of technology

Oil immerged transformer Aluminium coil

Device name
H59
Tension
15-20 K V / 410 V
Power
630 KVA
Equipment included

1 x Lockable adjustment switch located on the cover (operable without voltage) 3 x High-voltage plug-in bushings according to HN 52-S-61 4 x Low-voltage busbar-through bushings 2 x Earthing terminals on the cover 2 x Lifting and unhooking rings 1 x Nameplate in French 1 x Filling port 1 x Drainage device 1 x Low-voltage cover (capot BT) 1 x DGPT2 protection device 1 x Locking device

Contractual guarantee
1 YEAR
Country of origin
LEBANON