Description

CONSTRUCTION

 

A TUR panel consists of:

1 general load disconnecting device (visible break four-pole switch-disconnector)

 

Material intended for interior use

Metal frame made of pre-galvanized sheet metal

Four-pole (N, Ph1, Ph2, Ph3)

Assigned current depending on transformer power (800, 1200, or 1800 A)

Visible electric arc quenching in the air

Open switch: Automatic grounding of the transformer's neutral

Closed switch: Limitation of neutral overvoltages by a surge arrester (~10 kV)

Connection via lugs, cables in aluminum or copper

Panels can accommodate 4, 5, or 8 interchangeable Monobloc feeders

1 set of busbars (N, Ph1, Ph2, Ph3)

1 to 8 interchangeable Monobloc feeders equipped with HPC T2 fuse circuit breakers (excluding Neutral)

 

Four-pole assembly including 3 HPC T2 fuse circuit breakers (Ph1, Ph2, Ph3) up to 400 A

The Neutral is disconnectable via a rotating bar included in the feeder

Connection via lugs (mounted on aluminum or copper cables)

The Monobloc feeders are interchangeable

Monobloc feeders are bolted onto the TUR using an insulated wrench

Available fuses: 125 A, 160 A, 200 A, 250 A, 315 A, 400 A (according to HN 63-S-20 or IEC 60269)

 

FUNCTIONS

General isolation of the low voltage (BT)

Distribute electrical energy across multiple feeders

Protect each feeder/phase with fuses

Disconnect or isolate each feeder/phase

Features

Product range
TUR
Type of technology

Visible Break Switch-Disconnector

Device name
TUR8-1200
Tension
400 V
Nominal stream
1200 A
Equipment included

8 removable monobloc departures with screens, 1200A: Each departure is equipped with a removable screen for easy maintenance and handling. 1 isolation panel: For isolating the circuits safely during maintenance or repairs. Fuse door protectors: Devices that ensure fuse safety and provide protection from overcurrents. 1 insulated key: For secure and safe operation of the switches and equipment. Optional: - Knife fuse size 2: Standard knife-type fuse for high-current applications. - Tetrapolar protection for public lighting departure (ACG): Four-pole protection designed specifically for public lighting circuits. - Post lighting protection: Protection for the lighting circuits of distribution posts. - Reserve panels designed to replace a TUR departure: Additional panels that can replace a TUR departure, allowing for flexibility and future changes. - Isolation, short-circuiting, and testing panels: These panels are used to safely isolate, short-circuit, or test the circuits, allowing for secure maintenance, including during interventions.

Contractual guarantee
1 YEAR
Country of origin
FRANCE